PAT testing exam questions (City & Guilds 2377-77)

The City & Guilds 2377-77 PAT testing award ends with an online multiple-choice test: 50 questions in 1 hour 45 minutes, open book with the IET Code of Practice, and you need 80% to pass. This page sets out the format and what the test covers, then gives you 8 free practice questions with answers. Sparkwise has 273 like them, with explanations, and timed mocks in the same format.

Practise PAT 2377: get Sparkwise on Google Play Try 8 free questions

Free in the app: 101 PAT questions and one full mock. PAT 2377 unlock: £7.99 once for all 273 questions and every mock. No subscription. Android now; iPhone version not yet available.

On this page

The 2377-77 exam format

The Level 3 Award in the In-Service Inspection and Testing of Electrical Equipment (2377-77) has two parts, and you must pass both: an online knowledge test (2377-701) and a practical assignment (2377-702) where you inspect and test a Class I and a Class II item and complete the records. Sparkwise covers the online test.

Item2377-701 online test
Questions50 multiple choice
Time1 hour 45 minutes
Pass mark80%, which is 40 of 50
BookOpen book: a paper copy of the IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment, 5th edition
CalculatorA non-programmable scientific calculator
HowOn screen at an approved centre, on demand, invigilated
Sparkwise mock50 questions, 1 hour 45 minutes, 40 to pass, with the same topic mix

Source: the City & Guilds 2377-77 qualification handbook (v1.2) and its 2377 qualification page. Tabs, highlighting and short cross-references in your book are allowed; added notes and printed pages are not. Check the rules with your centre before the day.

What the exam covers

City & Guilds publishes how many of the 50 questions come from each learning outcome. Combined inspection and testing is more than a third of the paper, so it is where most marks are won or lost. Sparkwise mocks draw questions in the same proportions.

Learning outcomeQuestions in the real testQuestions in Sparkwise
Definitions in the Code of Practice426
Statutory and non-statutory requirements634
Units of measurement320
Construction classes and protection against shock841
User checks, frequency, risk assessment and formal visual inspection842
Combined inspection and testing: instruments, isolation, earth continuity, insulation, leakage, polarity and RCD tests1890
Recording information: records, registers and labels320

The law behind PAT is short: the Electricity at Work Regulations 1989 require equipment that could cause danger to be maintained, but they set no method or interval. The intervals and checks in the exam come from guidance such as HSE’s HSG107 and the Code of Practice, so questions often ask what the guidance suggests rather than what the law demands.

PAT mock: 50 questions, 1 h 45: A Sparkwise PAT 2377 mock test: question 1 of 50, open book, with the timer at 1:44:56

The same 50 questions, the same clock

The Sparkwise PAT mock runs for 1 hour 45 minutes, keeps time if you leave the app, lets you flag questions and come back, and reminds you that the test is open book. At the end you see your score against 40 of 50 and which areas cost you marks.

Get Sparkwise on Google Play

8 free PAT testing exam questions

One question from each Sparkwise PAT topic, with the answer and a short explanation. They are original questions written from HSE guidance, the law and public summaries of the Code of Practice, not the real City & Guilds questions: no app or website can show you those.

  1. Question 1 · Choose one answer

    A mobile phone charger is plugged into a 230 V socket. Which part is within the scope of in-service checks?

    1. The mains charger in the socket
    2. Only the phone's internal battery pack
    3. Only the phone screen and its casing
    4. Nothing, as phones are excluded entirely
    Show the answer

    Answer A: The mains charger in the socket

    Mains-powered battery chargers are portable equipment. The battery-powered phone itself is not, because it does not connect to the mains while in use.

    Source: INDG236 · portable and movable equipment

  2. Question 2 · Choose one answer

    Which PUWER 1998 regulation deals with inspection where deterioration of equipment could lead to danger?

    1. Regulation 4
    2. Regulation 9
    3. Regulation 22
    4. Regulation 6
    Show the answer

    Answer D: Regulation 6

    Regulation 6 requires inspection where safety depends on installation conditions or where equipment is exposed to conditions causing deterioration that could result in danger.

    Source: PUWER 1998 reg 6

  3. Question 3 · Choose one answer

    A lead's protective conductor measures 0.06 Ω. An identical lead twice as long would measure about what?

    1. 0.12 Ω
    2. 0.03 Ω
    3. 0.06 Ω
    4. 0.24 Ω
    Show the answer

    Answer A: 0.12 Ω

    Resistance is proportional to length, so doubling the length doubles the resistance: 0.06 × 2 = 0.12 Ω.

    Source: R ∝ length ÷ cross-sectional area

  4. Question 4 · Choose one answer

    What is fault protection?

    1. Protection against overloading a socket-outlet
    2. Protection against metal that becomes live after a fault
    3. Protection against touching live parts in normal use
    4. Protection against short circuits between line and neutral
    Show the answer

    Answer B: Protection against metal that becomes live after a fault

    Fault protection deals with exposed-conductive-parts made live by an insulation failure, for example through earthing and automatic disconnection, or double insulation.

    Source: BS 7671 Part 2 · fault protection

  5. Question 5 · Choose one answer

    According to HSG107, what combined inspection and test interval is suggested at first for an earthed (Class I) kettle?

    1. Never needed
    2. 1 to 2 years
    3. Every week
    4. 5 to 10 years
    Show the answer

    Answer B: 1 to 2 years

    HSG107 suggests 1 to 2 years for combined testing of Class I items such as kettles, with formal visual inspection every 6 months to 1 year and user checks.

    Source: HSG107 Table 1 · Class I

  6. Question 6 · Choose one answer

    Why is a high current earth continuity test preferred for robust equipment such as an electric fire?

    1. It removes corrosion from the earth terminals
    2. It stresses weak joints and connections
    3. It is quicker to set up than the low current test
    4. It also measures the insulation resistance
    Show the answer

    Answer B: It stresses weak joints and connections

    A high current can reveal weak strands or poor joints that a low current might pass. It is avoided only where electronics could be damaged.

    Source: IET CoP In-service · earth continuity

  7. Question 7 · Choose one answer

    Which condition must be met for a protective conductor current test?

    1. The equipment must be switched on and working
    2. The equipment must be disconnected from all supplies
    3. The equipment's fuse must be removed
    4. The equipment's earth must be disconnected
    Show the answer

    Answer A: The equipment must be switched on and working

    Leakage currents depend on the equipment operating, so it must be energised at normal voltage and switched on. Take care with moving parts and heat.

    Source: IET CoP In-service, 5th ed · leakage tests

  8. Question 8 · Select TWO answers

    Which TWO details would you expect to find in an equipment register entry? Select TWO.

    1. The equipment's location
    2. Its equipment class
    3. The tester's home address
    4. The price paid for the item
    Show the answer

    Answer A: The equipment's location, B: Its equipment class

    A register normally records identification, description, location, class and type, and inspection intervals. Personal or purchase details are not needed for safety.

    Source: C&G 2377-77 handbook · LO7 range

You’ve seen 8 of 273 questions for the PAT testing (2377-77)

The Sparkwise app has all 273 across 8 topics, each with an explanation and where to look, and 18 calculations have a step-by-step worked solution. It also has timed 50-question mocks of 1 hour 45 minutes with the 40-of-50 pass mark.

101 of them are free in the app. The PAT 2377 unlock is £7.99 one-off: every question and every mock for this exam. Or get All exams, £24.99 one-off: all 12 exams in Sparkwise and any exam added later. No subscription.

Get it on Google Play

Android now; iPhone version not yet available.

How to prepare for the online test

FAQ

How many questions are in the 2377-77 PAT testing exam?

The online knowledge test (2377-701) has 50 multiple-choice questions and lasts 1 hour 45 minutes. You need 80%, which is 40 of 50. You also have to pass the practical assignment (2377-702).

Is the PAT testing exam open book?

Yes. You can take a paper copy of the IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment (5th edition) and a non-programmable scientific calculator. Electronic copies are not allowed in the online test.

Are these the real 2377 exam questions?

No. Every question on this page and in Sparkwise is original, written from public sources on the same topics. Sparkwise is an independent app and is not linked to City & Guilds or the IET.

How much is PAT 2377 in Sparkwise?

Sparkwise is free to download, with 101 PAT questions and one full mock free. The PAT 2377 unlock is a one-off £7.99 for every question and mock. All exams, a one-off £24.99, unlocks all 12 exams in the app, including the 18th Edition and the 2391.

What should I study after PAT testing?

Electricians often move on to inspection and testing of installations. See our 2391 exam questions, or the 18th Edition exam guide if your wiring regulations qualification needs updating to BS 7671:2018+A4:2026.

Practise the C&G 2377-77 PAT testing exam in the Sparkwise app

273 original questions for the C&G 2377-77 PAT testing exam, each with an explanation and where to look, and timed 50-question mocks of 1 hour 45 minutes with the 40-of-50 pass mark. Spaced review brings back the questions you got wrong.

Free: two full topics and three questions in every other topic, and one full mock (101 questions).
PAT 2377, £7.99 one-off: every question and every mock for this exam.
All exams, £24.99 one-off: all 12 exams in Sparkwise and every exam we add later. No subscription.

Get it on Google Play

Android now; iPhone version not yet available. Sparkwise helps you prepare; it cannot promise a pass.

Where the exam facts come from

The format, time and pass mark above come from these public pages. Check them, or ask your centre, before you book.

Exam details can change. Sparkwise is not linked to any awarding or assessment body.